Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
ION8650 meter 128MB, 9S/29S/36S, 120VAC/160VDC 60Hz, Full comm 3I+4O, password
M8650A0C0H6C7B1A
ION8650 meter 128MB, 9S/29S/36S, 120VAC/160VDC 60Hz, Full comm 3I+4O, password
Specifications
Part Number M8650A0C0H6C7B1A
EAN 3606489637521
UNSPSC 83101808
Prop 65 This product can expose you to chemicals including: Dichloromethane (Methylene chloride) and Bisphenol A (BPA) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Depth 9.33 inch
Height 7.01 inch
Width 7.01 inch
Weight 15.43 pound
Characteristics
Range PowerLogic
Device Short Name ION8650A
Product Or Component Type Energy and power quality meter
Power Quality Analysis IEC 61000-4-15 flicker magnitude harmonic up to the 50th transient capture EN 50160 ed. 4 compliance report harmonic distortion voltage sag and swell detection waveform capture programmablity (logic and math functions) up to the 63rd harmonic IEC 61000-4-30 class A power quality measurement
Device Application Tariff metering Instrument transformer correction Equipment monitoring and control Demand and power factor control Energy pulsing and totalisation Co-generation and IPP monitoring Load curtailment
Type Of Measurement Current Voltage Frequency Apparent power total Power factor total Apparent power per phase Power factor per phase Active power total Active power per phase Reactive power total Reactive power per phase
Supply Voltage 120...277 V AC 47...63 Hz 65...120 V AC 47...63 Hz 80...160 V DC
Network Frequency 60 Hz
Outlet Standard American
In Rated Current 5 A 1 A 2 A
Type Of Network 1P + N 3P 3P + N
Power Consumption In Va 24 VA
Power Consumption In Va 33 VA
Display Type FSTN transflective LCD
Form Designation 9S 3-element 4 36S 2 1/2-element 4 29S 2 1/2-element 4
Sampling Rate 1024 samples/cycle
Measurement Current 0.001…24 A
Input Type current 0.01...20 A 0.05 Ohm)
Measurement Voltage 57…277 V AC phase to neutral 100…480 V AC phase to phase
Number Of Inputs 3 digital 0.001...100 mA 30 V DC
Measurement Accuracy Current 0.1 % Voltage 0.1 % Power 0.1 % Power factor 0.1 % Frequency 0.001 Hz Energy 0.1 %
Accuracy Class Class 0.2S energy IEC 62053-23 Class 0.2 energy ANSI C12.20 Class 0.2S energy IEC 62053-22
Number Of Outputs 2 pulse 4 form C relay output
Communication Port Protocol DNP3 300...115200 bauds ION 300...115200 bauds Ansi C12.18 <= 19200 bauds IEC 61850 ed. 2 10/100 Mbit/s TCP/IP 10/100 Mbit/s DLMS 300...115200 bauds Modbus 57600 bauds TCP/IP 300...57600 bauds DNP3 10/100 Mbit/s ION 10/100 Mbit/s Modbus RTU, master/slave 300...115200 bauds Modbus TCP, master/slave 10/100 Mbit/s ModemGate EtherGate
Communication Port Support RJ45 Ethernet SUB-D 9 RS485/RS232 Terminal block RS485 infrared RJ11 modem
Time Synchronisation Protocol IRIG-B GPS: Truetime/Datum
Data Recording Alarms Transient logs Revenue logs Event logs Data logs Harmonics logs Sag and swell logs GPS synchronisation Time stamping Historical logs
Transmission Rate 300...115200 bauds 300...57600 bauds 57600 bauds 10/100 Mbit/s <= 19200 bauds
Memory Capacity 128 MB
Web Services Port addressing user designed Alarm notification by e-mail Web server Robust security logs
Ethernet Service Enable/disable serial ports SNMP-Traps and SYSLOG Enable/disable Ethernet protocols
Tamperproof Of Settings Protected by access code Hardware lock by jumper
Compatibility Code ION8650A
Electromagnetic Compatibility Electrostatic discharge immunity test IEC 61000-4-2 Conducted RF disturbances IEC 61000-4-6 Immunity to impulse waves IEC 61000-4-12 Electrical fast transient/burst immunity test IEC 61000-4-4 Susceptibility to electromagnetic fields IEC 61000-4-3 1.2/50 µs shock waves immunity test IEC 61000-4-5 Conducted and radiated emissionsB CISPR 22
Mounting Mode Socket-mounted
Mounting Support Enclosure door
Type Of Installation Indoor installation
Overvoltage Category III
IP Degree Of Protection Front face IP65 Back IP51
Relative Humidity 5…95 %
Pollution Degree 2
Ambient Air Temp For Op -40…185 °F (-40…85 °C)
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Operating Altitude 0...9842.52 ft (0...3000 m)
Standards ANSI C12.1 IEC 62052-11
Width 7.01 in (178 mm)
Depth 9.33 in (237 mm)
Height 7.01 in (178 mm)
Product Weight 15.43 lb(US) (7 kg)
Nbr. Of Units In Pkg. 1
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews