Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
GUTOR PXC UL 25kVA, 600/208V ISO Transformer Dual Feed, Start Up
GUPXC25LFDIS
GUTOR PXC UL 25kVA, 600/208V ISO Transformer Dual Feed, Start Up
Specifications
Part Number GUPXC25LFDIS
Depth 31.50 inch
Height 82.68 inch
Width 47.24 inch
Weight 2034.87 pound
Characteristics
Lead Time Usually Ships within 6 Weeks
Provided Equipment Start-Up Service
Colour Light gray
Depth 31.50 in (80 cm)
Height 82.68 in (210 cm)
Product Weight 2034.87 lb(US) (923 kg)
Width 47.24 in (120 cm)
Network Frequency 60 Hz
Maximum Input Current 33 A
Max Short Time Withstd Current 50 kA
Input Harmonic Distortion Less than 5% for full load
Input Voltage 3 phase
Rated Power In W 25000 W
Max Configurable Power In W 25000 W
Harmonic Distortion Less than 2%
Output Frequency 60 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced
Wave Type Sine wave
Output Harmonic Distortion < 2% for 0 to 100% linear load and < 5% for full non-linear load
Output Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Bypass Type Built-in Bypass
Output Voltage 208 V 3 phase
Standards FCC Part 15 class A UL 1778
Ambient Air Temp For Op 32…104 °F (0…40 °C)
Relative Humidity 0…95 % non-condensing
Operating Altitude 0...3281 ft
Ambient Air Temp For Storage 5…104 °F (-15…40 °C)
Storage Altitude 0…16404 ft (0.00…4999.94 m)
Acoustic Level 65 dBA
Heat Dissipation 9901 Btu/h
Nema Degree Of Protection NEMA 1
IP Degree Of Protection IP42 with air filters
Battery Type External battery system
Free Slots 1
Preinstalled Device Network management card 2 with environmental monitoring, out of band access and Modbus
Control Panel Multi-function LCD status and control console
Alarm Audible and visible alarms prioritized by severity
Warranty 1 year on-site repair or replace with factory authorized Start-Up
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews