Part Number | GUPXC100FS |
---|---|
Depth | 31.50 inch |
Height | 82.68 inch |
Width | 47.24 inch |
Weight | 1728.43 pound |
Presentation | High performance, compact 3 phase UPS power protection standardized for light to heavy industrial applications and small to medium datacenters |
---|---|
Lead Time | Usually in Stock |
Provided Equipment | Start-Up Service |
Bypass Wiring Configuration | 5 wire (3PH + N + G) |
Colour | Light gray |
Depth | 31.50 in (80 cm) |
Height | 82.68 in (210 cm) |
Product Weight | 1728.43 lb(US) (784 kg) |
Width | 47.24 in (120 cm) |
Network Frequency | 60 Hz |
Number Of Input Connectors | 1 Hard Wire 5-wire (3PH + N + G) |
Input Voltage Limits | 208...253 V |
Inputvolt_Other | 220 V |
Maximum Input Current | 360 A |
Switching Current Capacity | 450 A |
Max Short Time Withstd Current | 65 kA |
Input Harmonic Distortion | Less than 5% for full load |
Input Protection Type | Upstream protection according to source |
Input Voltage | 3 phase |
Rated Power In W | 100000 W |
Max Configurable Power In W | 100000 W |
Harmonic Distortion | Less than 2% |
Output Frequency | 60 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced |
Outputvolt_Other | 220 V |
Crest Factor | Unlimited |
Ups Type | Double Conversion Online |
Wave Type | Sine wave |
Output Connector Type | Hard Wire 5-wire (3PH + N + G) 1 |
Output Voltage Tolerance | +/- 10% |
Output Harmonic Distortion | < 2% for 0 to 100% linear load and < 5% for full non-linear load |
Output Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
Bypass Type | Built-in Bypass |
Output Voltage | 208 V 3 phase |
Standards | FCC Part 15 class A UL 1778 |
Ambient Air Temp For Op | 14…104 °F (-10…40 °C) |
Relative Humidity | 0…95 % non-condensing |
Operating Altitude | 0...9842 ft |
Ambient Air Temp For Storage | 5…104 °F (-15…40 °C) |
Acoustic Level | 65 dBA |
Heat Dissipation | 28465 Btu/h |
Nema Degree Of Protection | NEMA 1 |
IP Degree Of Protection | IP42 with air filters |
Battery Type | External battery system |
Free Slots | 1 |
Preinstalled Device | Network management card 2 with environmental monitoring, out of band access and Modbus |
Control Panel | Multi-function LCD status and control console |
Alarm | Audible and visible alarms prioritized by severity |