Specifications
Part Number GVX1000K750NGS
Depth 35.43 inch
Height 77.56 inch
Width 153.54 inch
Weight 7074.99 pound
Characteristics
Presentation A highly efficient, modular, 750 kVA N+1 3-phase UPS that provides the performance, flexibility, and maximized asset utilization today’s large data centers and mission critical applications require. This EcoStruxure Ready UPS features up to 99% efficiency with patented ECOnversion technology. Includes 5x8 start-up service.
Lead Time Special Order - Call for Quoted Lead Times
Provided Equipment Installation guide Seismic compliance Start-Up Service Top and bottom cable entry
Colour White
Depth 35.43 in (90 cm)
Height 77.56 in (197 cm)
Product Weight 7074.99 lb(US) (3209.16 kg)
Width 153.54 in (390 cm)
Network Frequency 40 - 70 Hz
Number Of Input Connectors 1 Hard Wire 4-wire (3PH + G)
Input Voltage Limits 408...600 V
Max Short Time Withstd Current 100 kA
Input Harmonic Distortion Less than 3% for full load
Input Voltage 3 phase
Rated Power In W 750000 W
Max Configurable Power In W 750000 W
Output Frequency 60 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced
Crest Factor 3 : 1
Ups Type Double Conversion Online
Wave Type Sine wave
Output Connector Type Hard Wire 4-wire (3PH + G) 1
Output Voltage Tolerance +/- 1% symmetrical load and +/- 3% asymmetrical load
Output Harmonic Distortion < 2% linear load and < 3% non-linear load
Output Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Bypass Type Built-in Static Bypass Optional External Bypass
Output Voltage 480 V 3 phase
Product Certifications FCC part 15 class A UL 1778 5th edition
Standards CBC 2013 to Sds = 1.84g CSA C22.2 No 107.3 IBC 2012 IEC 62040-3 IEC 60721-4-2 Level 2M2 OSHPD
Ambient Air Temp For Op 32…104 °F (0…40 °C)
Relative Humidity 0…95 % non-condensing
Ambient Air Temp For Storage 5…104 °F (-15…40 °C)
Acoustic Level 72 dBA
Heat Dissipation 142167 Btu/h
IP Degree Of Protection IP20
Battery Type External battery system
Discharge Battery Voltage 384 V DC
Free Slots 1
Control Panel Touch Screen LCD User Interface
Alarm Audible and visible alarms prioritized by severity
Emergency Power Off Optional
Warranty 1 year on-site repair or replace with factory authorized Start-Up