Part Number | GVSUPS15KB4FS |
---|---|
Depth | 33.35 inch |
Height | 58.46 inch |
Width | 20.51 inch |
Weight | 1014.13 pound |
Presentation | Highly efficient, easy-to-deploy 15kW, 208V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and 2 smart high-capacity modular battery strings, expandable to 4 strings for extended runtime. Runtime charts available in the Documents tab. |
---|---|
Lead Time | Usually Ships within 2 Weeks |
Provided Equipment | Dust filter Installation guide Integrated network management Power modules ship installed Start-Up Service Top and bottom cable entry |
Bypass Voltage Tolerance | +/- 10 % |
Surface Finish | Gloss level 85% |
Colour | White RAL 9003) |
Depth | 33.35 in (84.7 cm) |
Height | 58.46 in (148.5 cm) |
Product Weight | 1014.13 lb(US) (460 kg) |
Width | 20.51 in (52.1 cm) |
Network Frequency | 40 - 70 Hz |
Input Voltage Limits | 177...239 V 208 V |
Inputvolt_Other | 200 V 220 V |
Maximum Input Current | 54 A |
Max Short Time Withstd Current | 65 kA |
Input Harmonic Distortion | Less than 3% for full load |
Input Voltage | 3 phase |
Rated Power In W | 15000 W |
Max Configurable Power In W | 15000 W |
Output Frequency | 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal not synced 60 Hz +/- 0.1 % for 60 Hz nominal not synced |
Outputvolt_Other | 200 V 220 V |
Crest Factor | 2.5 |
Ups Type | Double Conversion Online |
Wave Type | Sine wave |
Output Voltage Tolerance | +/-1% after 50ms |
Output Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
Bypass Type | Built-in Static Bypass |
Output Voltage | 208 V 3 phase |
Standards | CSA C22.2 No 107.3 FCC Part 15 class A IEC 62040-3 IEC 60721-4-2 Level 2M2 UL 1778 5th edition |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) |
Relative Humidity | 0…95 % non-condensing |
Operating Altitude | 0...3281 ft |
Ambient Air Temp For Storage | 5…104 °F (-15…40 °C) |
Storage Altitude | 0…10000 ft (0.00…3048.00 m) |
Acoustic Level | 61 dBA |
Heat Dissipation | 3059 Btu/h |
IP Degree Of Protection | IP20 |
Battery Type | VRLA |
Battery Voltage | 480V |
Discharge Battery Voltage | 384 V DC |
Max Current Discharge | 41 A |
Free Slots | 1 |
Control Panel | Touch Screen LCD User Interface |
Alarm | Audible and visible alarms prioritized by severity |
EU RoHs Directive | Under investigation |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366