Part Number | GVMRB225KG65S |
---|---|
UPC | 731304326533 |
UPC11 | 73130432653 |
EAN | 0731304326533 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
Depth | 33.62 inch |
Height | 77.56 inch |
Width | 39.45 inch |
Weight | 1552.06 pound |
Presentation | Highly compact, energy efficient, redundant 3-phase UPS for data center, facility and industrial applications. |
---|---|
Lead Time | Usually Ships within 2 Weeks |
Provided Equipment | Dust filter Installation guide Integrated network management Seismic compliance Start-Up Service Top and bottom cable entry |
Bypass Voltage Tolerance | +/-10% settable from +/-4/6/8 and 10% |
Max Bypass Input Current | 350 A |
Bypass Current Protection | 400 A |
Colour | White |
Depth | 33.62 in (85.4 cm) |
Height | 77.56 in (197 cm) |
Product Weight | 1552.06 lb(US) (704 kg) |
Width | 39.45 in (100.2 cm) |
Network Frequency | 40 - 70 Hz |
Input Voltage Limits | 360...576 V adjustable 480 V 360...576 V 480 V |
Maximum Input Current | 347 A |
Max Short Time Withstd Current | 65 kA |
Input Harmonic Distortion | Less than 3% for full load |
Input Protection Type | 3-pole breaker |
Input Voltage | 3 phase |
Rated Power In W | 202500 W |
Max Configurable Power In W | 202500 W |
Harmonic Distortion | Less than 2% |
Output Frequency | 50/60 Hz +/- 1 Hz sync to mains 50/60 Hz +/- 1 Hz not synced |
Crest Factor | Unlimited |
Ups Type | Double Conversion Online |
Wave Type | Sine wave |
Output Connector Type | Hard Wire 4-wire (3PH + G) 1 Hard Wire 5-wire (3PH + N + G) 1 |
Output Voltage Tolerance | +/- 1% static and +/- 3% at 100% load step |
Output Harmonic Distortion | < 2% linear load and < 3% non-linear load |
Output Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
Neutral Output Current | 244 A |
Bypass Type | Built-in Static Bypass |
Output Voltage | 480 V 3 phase |
Product Certifications | CUL Listed ENERGY STAR V2.0 (USA) |
Standards | EN/IEC 62040-3 FCC Part 15 class A IBC 2012 and CBC2013 to Sds=2.02g OSHPD UL 1778 |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) |
Relative Humidity | 0…95 % |
Operating Altitude | 0...3333 ft |
Ambient Air Temp For Storage | -13…131 °F (-25…55 °C) |
Storage Altitude | 0…49212 ft (0.00…14999.82 m) |
Acoustic Level | 65 dBA |
Heat Dissipation | 27670 Btu/h |
IP Degree Of Protection | IP20 |
Battery Type | External battery system |
Battery Voltage | 480V |
Discharge Battery Voltage | 384 V |
Short-Circuit Current | 65 kA |
Max Current Discharge | 549 A |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366