Part Number | SUG580S90UL |
---|---|
UPC | 731304302926 |
UPC11 | 73130430292 |
EAN | 0731304302926 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
Depth | 32.01 inch |
Height | 75.00 inch |
Width | 173.82 inch |
Weight | 14975.42 pound |
Presentation | UPS and three UL 924 listed matching battery cubicles with a minimum of 90 minutes battery operation. |
---|---|
Lead Time | Usually Ships within 2 Weeks |
Provided Equipment | Installation guide |
Depth | 32.01 in (81.3 cm) |
Height | 75.00 in (190.5 cm) |
Product Weight | 14975.42 lb(US) (6792.73 kg) |
Width | 173.82 in (441.5 cm) |
Network Frequency | 45...65 Hz |
Number Of Input Connectors | 1 Hard Wire 4-wire (3PH + G) |
Input Voltage Limits | 408...552 V 480 V |
Maximum Input Current | 154 A |
Switching Current Capacity | 250 A |
Max Short Time Withstd Current | 20 kA |
Input Harmonic Distortion | Less than 3% for full load |
Input Protection Type | 3-pole breaker |
Input Voltage | 3 phase 3 phase |
Rated Power In W | 72000 W |
Max Configurable Power In W | 72000 W |
Harmonic Distortion | Less than 2% |
Output Frequency | 60 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced |
Crest Factor | 3 : 1 |
Ups Type | Double Conversion Online |
Wave Type | Sine wave |
Output Connector Type | Hard Wire 4-wire (3PH + G) 1 |
Output Voltage Tolerance | +/- 1% static and +/- 2 % at 100% load step |
Output Harmonic Distortion | < 1% linear load and < 2.5% non-linear load |
Output Overload Operation | 10 minutes @ 125% and 30 seconds @ 150% |
Bypass Type | Internal Bypass (Automatic and Manual) Optional External Bypass |
Output Voltage | 480 V 3 phase 600 V 3 phase |
Product Certifications | UL 1778 UL 924 Listed |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) |
Relative Humidity | 0…95 % |
Operating Altitude | 0...3333 ft |
Ambient Air Temp For Storage | -4…113 °F (-20…45 °C) |
Storage Altitude | 0…40000 ft (0.00…12192.00 m) |
Acoustic Level | 63 dBA |
Heat Dissipation | 19791 Btu/h |
IP Degree Of Protection | IP20 |
Battery Type | External battery system |
Free Slots | 3 |
Control Panel | Multi-function LCD status and control console |
Emergency Power Off | Optional |
GTIN | 00731304302926 |
EU RoHs Directive | Compliant |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366