DOE 2016 LV XFMR, 3 Phase, 112.5kVA, 208 Delta-208Y/120, AL, 150°C Rise-220C INS
EX300T211H
DOE 2016 LV XFMR, 3 Phase, 112.5kVA, 208 Delta-208Y/120, AL, 150°C Rise-220C INS
Specifications
Part Number EX300T211H
Availability N
Lead Time 30
UNSPSC 39121001
Prop 65 This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule PE2X
Return Indicator No
Depth 32.76 inch
Height 57.52 inch
Width 40.08 inch
Weight 1860.00 pound
Characteristics
Range Of Product Square D
Product Or Component Type DOE 2016 energy efficient transformer
Device Application Low voltage electrical distribution
Box Number 25J
Network Number Of Phases 3 phase
Rated Opr Power In VA 300 kVA
Network Frequency 60 Hz
Type Of Cooling Natural convection
Primary Voltage 208 V delta
Number Of Tap-Offs 1 5 % FCAN 2 5 % FCBN
Secondary Voltage 208Y/120 V
Coil Material Aluminium
Basic Imp Level (Bil) 10 kV
Temperature Rise 150 °C 220 °C insulated
Doe Efficiency 99.13 % at 35 % load factor , 167 °F (75.0 °C)
Sound Level 6 dB NEMA ST-20 49 dB
%Iz 4.4 %
%Ix 0.0411 %
X/R Ratio 2.59
Let Through Current 18.9 kA
Transformer Losses 445.0 no load (core loss) 4756.0 load loss (coil loss)
Transformer Btu/Hr 1965.5860184317119 16.6 % 2532.6623995 0.25 % 5575.440028 0.5 % 10646.736075499999 0.75 % 17746.550541999997 1.0 %
Height 57.52 in (1461 mm)
Depth 32.76 in (832 mm)
Width 40.08 in (1018 mm)
Product Weight 1860.00 lb(US) (843.68 kg)
Mounting Support Floor Floor, with 7400FMB
Degree Of Protection UL type 1 UL type 2, with 7400DS25J UL type 3R, with 7400WS25J
Electrical Connection 6 Hole Nema Pad secondary 0.44 in (11.1 mm) 8 Hole Nema Pad sec - XO 0.44 in (11.1 mm) 2 x 4 Hole Nema Pad primary 0.44 in (11.1 mm)
Ambient Air Temp For Op 104 °F (40 °C)
Average Ambient Air Temp F Opr 30 °C
Standards UL 1561 CSA C22.2 No 47 NEMA ST-20
Category 16501 - EX MTO 300KVA SPECIAL VOLTAGE
Discount Schedule PE2X
Nbr. Of Units In Pkg. 1
Green Premium Status Green Premium product
REACh Free Of SVHC Yes
EU RoHs Directive Compliant
Toxic Heavy Metal Free Yes
Mercury Free Yes
Pvc Free Yes
Halogen Content Performance Halogen free plastic parts product