| Part Number | BMXSRA0405 |
|---|---|
| Country of Origin | FR |
| UPC | 785901968566 |
| UPC11 | 78590196856 |
| EAN | 3606481204936 |
| Availability | N |
| Lead Time | 10 |
| UNSPSC | 26101205 |
| HTs Code | 8536490080 |
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | PC34 |
| Return Indicator | Yes |
| Weight | 0.32 pound |
| Range Of Product | Modicon X80 |
|---|---|
| Product Or Component Type | Discrete output module |
| Discrete Output Number | 4 EN/IEC 61131-2 |
| Discrete Output Type | Relay |
| Discrete Output Voltage | 24...240 V 10...264 V AC 12...24 V 10...34 V DC |
| Ith Cnvtl Free Air Therm Crrt | 3 A |
| Insulation Resistance | > 10 MOhm 500 V DC |
| Power Dissipation In W | 3.9 W |
| Response Time On Output | 12 ms activation 6 ms deactivation |
| Typical Current Consumption | 240 mA 3.3 V DC 130 mA 24 V DC |
| Mtbf Reliability | 474792 H |
| Protection Type | External short-circuit protection overvoltage protection, inductive AC overvoltage protection, inductive DC External overload protection |
| Output Overload Protection | Use 1 fast blow fuse per channel or group of channel |
| Output Overvoltage Protct | Use discharge diode on each output DC Use RC circuit on each output AC Use ZNO surge limiter on each output AC |
| Output Short-Circuit Protct | Use 1 fast blow fuse per channel or group of channel |
| Minimum Switching Current | 10 mA 5 V DC |
| Maximum Switching Voltage | 230 V AC |
| Mechanical Durability | 10000000 cycles |
| Electrical Durability | AC-15 80000 cycles 250 VA 250 V -13…140 °F (-25…60 °C) AC-15 80000 cycles 500 VA 250 V -13…140 °F (-25…60 °C) AC-15 80000 cycles 750 VA 250 V -13…140 °F (-25…60 °C) AC-12 250000 cycles 250 VA 250 V -13…140 °F (-25…60 °C) AC-12 70000 cycles 500 VA 250 V -13…140 °F (-25…60 °C) AC-12 30000 cycles 1000 VA 250 V -13…140 °F (-25…60 °C) DC-13 80000 cycles 24 VA 24 V -13…140 °F (-25…60 °C) DC-13 50000 cycles 48 VA 24 V -13…140 °F (-25…60 °C) DC-13 30000 cycles 96 VA 24 V -13…140 °F (-25…60 °C) DC-12 1000000 cycles 24 VA 24 V -13…140 °F (-25…60 °C) DC-12 500000 cycles 48 VA 24 V -13…140 °F (-25…60 °C) DC-12 300000 cycles 120 VA 24 V -13…140 °F (-25…60 °C) |
| Switching Frequency | <= 50 Hz |
| Status Led | Module operating (RUN) 1 LED Green) Channel diagnostic 1 LED per channel Green) Module error (ERR) 1 LED Red) Module I/O 1 LED Red) |
| Product Weight | 0.32 lb(US) (0.145 kg) |
| IP Degree Of Protection | IP20 |
| Product Certifications | Merchant Navy ATEX EAC TÜV UL CSA |
| Standards | UL 61010-2-201 EN/IEC 61131-2 EN/IEC 61010-2-201 CSA C22.2 No 61010-2-201 |
| Dielectric Strength | 2000 V AC 50/60 Hz 1 min |
| Vibration Resistance | 3 gn |
| Shock Resistance | 15 gn |
| Ambient Air Temp For Storage | -40…185 °F (-40…85 °C) |
| Ambient Air Temp For Op | -13…140 °F (-25…60 °C) |
| Relative Humidity | 5…95 % 131 °F (55 °C) without condensation |
| Protective Treatment | Conformal coating |
| Environmental Characteristic | Gas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2 Fungal spore resistant class 3B2 |
| Operating Altitude | 0...6561.68 ft (0...2000 m) 2000...5000 m with derating factor |
| Category | 18161 - MODICON M580 CONTROLLERS HSBY |
| Discount Schedule | PC34 |
| GTIN | 00785901968566 |
| Nbr. Of Units In Pkg. | 1 |
| Country Of Origin | FR |
| Green Premium Status | Green Premium product |
| EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
| Mercury Free | Yes |
| WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |