Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Direct online starter, TeSys island, 80A AC-1, 66A AC-3, 37kW / 40hp
TPRST080
Direct online starter, TeSys island, 80A AC-1, 66A AC-3, 37kW / 40hp

TeSys island direct starter, 3 poles, 80A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 80A and motors up to 37kW@400V / 40hp@480V. It provides motor protection functions including thermal overload (setting 4-80A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number TPRST080
EAN 3606489832780
Availability N
Lead Time 20
ECCN EAR99
HTs Code 8536504000
RoHS Compliant Yes
Discount Schedule I12
Return Indicator No
Depth 4.92 inch
Height 6.57 inch
Width 2.17 inch
Weight 2.75 pound
Characteristics
Range TeSys
Product Name TeSys island
Device Short Name TPRST
Product Or Component Type Motor starter
Motor Starter Type Direct on line
Device Presentation Direct starter connected to an automation controller through a bus coupler Operational only when connected to a bus coupler
Function Available Upstream voltage presence detection Electrical line and load protection Power and energy monitoring when connected with TPRVM voltage module
Product Compatibility TPRBC bus coupler TPRVM voltage interface module
Poles Description 3P 3 NO
Utilisation Category AC-1 AC-2 AC-3 AC-4
Motor Power kW 18.5 kW 230 V 50 Hz AC-3) 37 kW 380...415 V 50 Hz AC-3) 37 kW 440 V 50 Hz AC-3) 37 kW 500 V 50 Hz AC-3) 37 kW 690 V 50 Hz AC-3)
Motor Power Hp (Ul / Csa) 5 hp 120 V AC 60 Hz 1 phase 10 hp 240 V AC 60 Hz 1 phase 20 hp 208 V AC 60 Hz 3 phase 20 hp 240 V AC 60 Hz 3 phase 40 hp 480 V AC 60 Hz 3 phase 50 hp 600 V AC 60 Hz 3 phase
Ue Rated Operational Voltage <= 690 V AC 47...63 Hz
Ie Rated Operational Current 66 A 122 °F (50 °C)) <= 440 V AC-3 80 A 122 °F (50 °C)) <= 440 V AC-1
Ith Cnvtl Free Air Therm Crrt 80 A 122 °F (50 °C)
Ui Rated Insulation Voltage 690 V IEC 60947-4-1 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1
Uimp Rated Imp Wstd Voltage 6 kV IEC 60947-1
Overvoltage Category III
Thermal Protection Adj Range 4…80 A
Thermal Overload Class Class 5…30
Reset Remotely or automatically
Irms Rated Making Capacity 1000 A 440 V IEC 60947
Rated Breaking Capacity 1000 A 440 V IEC 60947
Icw Rated Short-Time Wstd Crrt 900 A 104 °F (40 °C) - 1 s 520 A 104 °F (40 °C) - 10 s 260 A 104 °F (40 °C) - 1 min 110 A 104 °F (40 °C) - 10 min
Average Impedance 1.5 mOhm - Ith 80 A 50 Hz
Power Dissipation Per Pole 6.5 W AC-3 9.6 W AC-1
Uc Control Circuit Voltage 24 V DC supplied by the bus coupler
Current Consumption 80 mA contactor sealed 500 mA contactor closing
Power Dissipation In W 21.4 W at Ie
Mechanical Durability 6 Mcycles
Electrical Durability 0.75 Mcycles 66 A AC-3 440 V 0.5 Mcycles 80 A AC-1 440 V
Operating Rate 3600 cyc/mn AC-3
Operating Time < 80 ms closing < 80 ms opening
Safety Performance Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Protection Type Thermal overload protection Motor overheat Overcurrent Undercurrent Jam Long start Stall Rapid cycle lockout Rapid restart lockout Phase sequence Phase loss Phase reversal Phase unbalance Ground current
Monitoring Type Time device ON Time device switch ON Number of faults Number of switching cycles Number of device power cycles Average current Iavg Average voltage Vavg Max current Imax Max voltage Vmax Active and reactive power with voltage module Active and reactive energy with voltage module True power factor with voltage module
Local Signalling DS (device status) 1 LED green/red) LS (load status) 1 LED green/red)
Standards EN/IEC 60947-1 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
Product Certifications UL CSA CCC EAC
Mounting Mode Horizontal and vertical 35 mm symmetrical DIN rail)
Connections - Terminals EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²) AWG 16...AWG 2)rigid EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²) AWG 16...AWG 4)rigid EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²) AWG 16...AWG 2)flexible without cable end EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²) AWG 16...AWG 4)flexible without cable end EverLink BTR screw connectors 1 0.00…0.05 in² (1…35 mm²) AWG 16...AWG 2)flexible with cable end EverLink BTR screw connectors 2 0.00…0.04 in² (1…25 mm²) AWG 16...AWG 4)flexible with cable end
Tightening Torque 44.25 lbf.in (5 N.m) 0.00…0.04 in² (1…25 mm²) hexagonal 0.16 in (4 mm) 70.81 lbf.in (8 N.m) 0.04…0.05 in² (25…35 mm²) hexagonal 0.16 in (4 mm)
Width 2.17 in (55 mm)
Height 6.57 in (167 mm)
Depth 4.92 in (125 mm)
Product Weight 2.75 lb(US) (1.248 kg)
Ambient Air Temp For Storage -13…158 °F (-25…70 °C)
Ambient Air Temp For Op 14…122 °F (-10…50 °C) without derating 122…140 °F (50…60 °C) with current derating
Relative Humidity 5…95 %
Operating Altitude 0...6561.68 ft (0...2000 m) without derating
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews