This Schneider Electric Zelio Logic SR2 discovery pack compact smart relay / programmable controller uses a supply voltage of 24 volts direct current, has 12 inputs / outputs with screw-clamp terminals and has an integrated LCD display. This compact programmable relay discovery pack is ideal for discovering the Zelio Logic range of programmable smart relays. It has compact form-factor, allowing installation on DIN rail. It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons. Discovery package includes one copy of Zelio Soft and one USB cable to connect the relay to your PC. Simple ladder programming, adapted for non-specialists. Discovery package, coming with Zelio Soft programming software, the simplest way to learn and use this relay. Built-in EEPROM flash memory for data backup up to 10 years, easy-to-recover after a power shortage or incident.
Brand: Telemecanique
Add to Quote CataloguePart Number | SR2PACKBD |
---|---|
Country of Origin | FR |
UPC | 785901693857 |
UPC11 | 78590169385 |
EAN | 3389110549386 |
Availability | S |
Lead Time | 33 |
UNSPSC | 39122331 |
ECCN | EAR99 |
HTs Code | 8536490080 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | I |
Return Indicator | Yes |
Weight | 1.54 pound |
Range Of Product | Zelio Logic |
---|---|
Product Or Component Type | Compact discovery packs |
Discrete Input Number | 8 EN/IEC 61131-2 type 1 |
Number Of Outputs | 4 relay |
Kit Composition | SR2B121BD Cable PC SR2USB01 for connection to PC Zelio Soft 2 programming software CD-ROM |
Input/Output Number | 12 |
Local Display | With |
Number Or Control Scheme Lines | 120 ladder 0…200 FBD |
Cycle Time | 6…90 ms |
Backup Time | 10 years 77 °F (25 °C) |
Clock Drift | 12 min/year 32…131 °F (0…55 °C) 6 s/month 77 °F (25 °C) |
Checks | Program memory on each power up |
Us Rated Supply Voltage | 24 V |
Supply Voltage Limits | 19.2…30 V |
Supply Current | 100 mA without extension) |
Power Dissipation In W | 3 W without extension |
Reverse Polarity Protection | With |
Discrete Input Type | Resistive |
Discrete Input Voltage | 24 V DC |
Discrete Input Current | 4 mA |
Counting Frequency | 1 kHz discrete input |
Voltage State 1 Guaranteed | >= 15 V I1...IA and IH...IR discrete input circuit >= 15 V IB...IG used as discrete input circuit |
Voltage State 0 Guaranteed | <= 5 V I1...IA and IH...IR discrete input circuit <= 5 V IB...IG used as discrete input circuit |
Current State 1 Guaranteed | >= 1.2 mA IB...IG used as discrete input circuit) >= 2.2 mA I1...IA and IH...IR discrete input circuit) |
Current State 0 Guaranteed | <= 0.5 mA IB...IG used as discrete input circuit) <= 0.75 mA I1...IA and IH...IR discrete input circuit) |
Input Compatibility | 3-wire proximity sensors PNP discrete input |
Analogue Input Number | 4 |
Analogue Input Type | Common mode |
Analogue Input Range | 0...10 V 0...24 V |
Maximum Permissible Voltage | 30 V analogue input circuit |
Analogue Input Resolution | 8 bits |
Lsb Value | 39 mV analogue input circuit |
Conversion Time | Smart relay cycle time analogue input circuit |
Conversion Error | +/- 5 % 77 °F (25 °C) analogue input circuit +/- 6.2 % 131 °F (55 °C) analogue input circuit |
Repeat Accuracy | +/- 2 % 131 °F (55 °C) analogue input circuit |
Operating Distance | 10 m between stations, with screened cable (sensor not isolated) analogue input circuit |
Input Impedance | 12 kOhm IB...IG used as analogue input circuit 12 kOhm IB...IG used as discrete input circuit 7.4 kOhm I1...IA and IH...IR discrete input circuit |
Output Voltage Limits | 24...250 V AC relay output) 5...30 V DC relay output) |
Contacts Type And Composition | NO relay output |
Output Thermal Current | 8 A for all 4 outputs relay output |
Electrical Durability | AC-12 500000 cycles 230 V, 1.5 A relay output EN/IEC 60947-5-1 AC-15 500000 cycles 230 V, 0.9 A relay output EN/IEC 60947-5-1 DC-12 500000 cycles 24 V, 1.5 A relay output EN/IEC 60947-5-1 DC-13 500000 cycles 24 V, 0.6 A relay output EN/IEC 60947-5-1 |
Switching Capacity In Ma | >= 10 mA 12 V relay output) |
Operating Rate In Hz | 0.1 Hz at Ie)relay output 10 Hz no load)relay output |
Mechanical Durability | 10000000 cycles relay output |
Uimp Rated Imp Wstd Voltage | 4 kVEN/IEC 60947-1 and EN/IEC 60664-1 |
Clock | With |
Response Time | 10 ms from state 0 to state 1)relay output 5 ms from state 1 to state 0)relay output |
Connections - Terminals | screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end |
Tightening Torque | 4.43 lbf.in (0.5 N.m) |
Overvoltage Category | III EN/IEC 60664-1 |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366