| Part Number | LV839069 |
|---|---|
| UPC | 606489419837 |
| UPC11 | 60648941983 |
| EAN | 3606489419837 |
| UNSPSC | 39121601 |
| Depth | 16.80 inch |
| Height | 17.28 inch |
| Width | 17.49 inch |
| Product Name | Masterpact MTZ2 |
|---|---|
| Device Short Name | MTZ2 08 L1 |
| Product Or Component Type | Circuit breaker |
| Device Application | Protection |
| Poles Description | 3P |
| Network Type | AC |
| Network Frequency | 50/60 Hz |
| Rating Code | L1 |
| Control Type | Push-button |
| Mounting Mode | Drawout |
| Mounting Support | Base plate Rails |
| In Rated Current | 800 A 104 °F (40 °C) |
| Circuit Breaker Ct Rating | 800 A |
| Performance Level | 200 kA Icu 254 V AC 60 Hz ANSI C37.50 200 kA Icu 508 V AC 60 Hz ANSI C37.50 130 kA Icu 635 V AC 60 Hz ANSI C37.50 200 kA Icu 254 V AC 50 Hz ANSI C37.50 150 kA Icu 508 V AC 50 Hz ANSI C37.50 100 kA Icu 635 V AC 50 Hz ANSI C37.50 |
| Mechanical Durability | 12500 cycles ANSI C37.50 |
| Electrical Durability | 2800 cycles ANSI C37.50 |
| Connection Pitch | 4.53 in (115 mm) |
| Icw Rated Short-Time Wstd Crrt | 30 kA 0.5 s ANSI C37.50 |
| Integ Instant Protection | 49.5…55.5 kA |
| Rated Brking And Making Cap | 55 kA |
| Maximum Breaking Time | 9 ms |
| Closing Response Time | 70 ms |
| Height | 17.28 in (438.8 mm) |
| Width | 17.49 in (444.3 mm) |
| Depth | 16.80 in (426.8 mm) |
| GTIN | 03606489419837 |