Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
BCPM power monitoring advanced + 2 adapter boards – 42 split core CT (not incld)
BCPMSCAY63S
BCPM power monitoring advanced + 2 adapter boards – 42 split core CT (not incld)

This is an integrated solution for monitoring multi-circuits and mains by using a single meter. The meter is designed for retrofit and is used for critical power operations in data centres and energy management in buildings. It offers class 1 (1 %) power and energy system accuracy (including 50A, 100A or 200A split-core current transformers) on all branch channels. The BCPM monitors both the 42 branch circuits and mains values, incoming power and energy. All to provide information on the complete Power Distribution Unit. Adapter boards with terminals for split-core CTs are mounted on the same plate as the main board. Full alarming capabilities ensure that potential issues are dealt with before they become problems. Communication enabled with a RS485 serial port and the Modbus protocol support, more communication options with the gateway H8951. The meter need to be powered by a 90V AC to 277V AC supply source. This version is for 42 circuits, but do not include branch current transformers nor ribbon. The device dimensions are 228mm in width, 146mm in height and weight 1.5 kilograms.

Add to Quote Catalogue
Specifications
Part Number BCPMSCAY63S
UPC 606480566875
UPC11 60648056687
EAN 3606480566875
Availability N
Lead Time 15
Prop 65 This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
Discount Schedule PL1
Return Indicator No
Height 5.75 inch
Width 11.34 inch
Weight 3.31 pound
Characteristics
Range PowerLogic
Product Name PowerLogic BCPMSC
Product Or Component Type Multi-circuit energy meter
Device Short Name BCPMSCA
Model Type Advanced
Power Monitoring Basic instrumentation
Energy Management Sub billing and cost allocation
Device Application Sub billing
Power Quality Analysis voltage sag and swell detection
Type Of Measurement Voltage Current Frequency Active power Power factor Active energy
[Us] Rated Supply Voltage 90...277 V AC 50/60 Hz +/- 1 %
Network Frequency 60 Hz 50 Hz
Current Transformer Input 42 split core CT 0.333 V
Update Time 1.8 s
Measurement Voltage 90…277 V phase to neutral 150…480 V phase to phase
Measurement Accuracy Branch current 2 % 0.25…2 A Branch current 1 % 2…100 A Mains current 3 % 1…100 % Mains current 3 % 2…100 % Voltage 1 % 90…277 V
Sampling Rate 256 samples/cycle
Provided Equipment 2 x cables 2 x adapter board Bracket for support
Communication Port Protocol Modbus RTU
Communication Port Support RS485
Communication Of Data High current alarm Low current alarm High-high current alarm Under voltage alarm Low-low current alarm Over voltage alarm
Mounting Mode Fixed
Mounting Support Bracket
Relative Humidity 0…95 % 32…140 °F (0…60 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Operating Altitude 9842.52 ft (3000 m)
Standards EN 61010 ANSI C12.1 UL 508 IEC 61036
Product Certifications UL
Width 11.34 in (288 mm)
Height 5.75 in (146 mm)
Product Weight 3.31 lb(US) (1.5 kg)
Category 09793 - PLOGIC BRANCH CIRCUIT BCPM & MCM
Discount Schedule PL1
GTIN 03606480566875
Nbr. Of Units In Pkg. 1
EU RoHs Directive Compliant
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Documents