TeSys B contactor, 3 poles (3NO), 1500A/1000V AC-3, for motor control applications up to 750kW@400V and non-inductive load applications up to 2000A/1000V. Predefined composition bar contactor, it provides a 110V 50-400Hz AC coil, 2NO+2NC auxiliary contacts, bolt terminals for bars. For operating rates until 120 cycles/hour and environments until 55°C, it procures high reliability and durability. Multi standards certified (IEC, CSA, Marine) and Green Premium compliant (RoHS/REACh).
Add to Quote CataloguePart Number | LC1BP33F22 |
---|---|
Country of Origin | FR |
UPC | 389110103069 |
UPC11 | 38911010306 |
EAN | 3389110103069 |
Availability | N |
Lead Time | 35 |
ECCN | EAR99 |
HTs Code | 8536490065 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | I12 |
Return Indicator | No |
Depth | 18.70 inch |
Height | 19.29 inch |
Width | 31.10 inch |
Weight | 207.23 pound |
Range | TeSys |
---|---|
Product Name | TeSys B |
Product Or Component Type | Contactor |
Device Short Name | LC1BP |
Contactor Application | Motor-heating-lighting |
Utilisation Category | AC-3 AC-4 AC-1 |
Control Circuit Type | AC |
Coil Type | Standard |
Poles Description | 3P |
Pole Contact Composition | 3 NO |
Ie Rated Operational Current | 2000 A 104 °F (40 °C)) AC AC-1 power circuit 1500 A 131 °F (55 °C)) AC AC-3 power circuit |
Motor Power kW | 425 kW 220...230 V AC 50/60 Hz AC-3) 670 kW 1000 V AC 50/60 Hz AC-3) 700 kW 500 V AC 50/60 Hz AC-3) 750 kW 380...400 V AC 50/60 Hz AC-3) 750 kW 660...690 V AC 50/60 Hz AC-3) 800 kW 415 V AC 50/60 Hz AC-3) 800 kW 440 V AC 50/60 Hz AC-3) 220 kW 400 V AC 50/60 Hz AC-4) |
Auxiliary Contact Composition | 2 NO + 2 NC |
[Uc] Control Circuit Voltage | 110 V AC 50/60 Hz |
Ctrl Circuit Voltage Limits | Operational 0.85...1.1 Uc 50/60 Hz Drop-out 0.35...0.5 Uc 50/60 Hz |
Ui Rated Insulation Voltage | 1000 V - power circuit IEC 60158-1 1000 V - power circuit IEC 60947-4 1500 V - power circuit VDE 0110 group C |
Mounting Mode | Fixed |
Mounting Support | Notched mounting rails Bar support bracket |
Connections - Terminals | Power circuit bolted connection |
Tightening Torque | Power circuit 309.78 lbf.in (35 N.m) bars |
Ue Rated Operational Voltage | Power circuit <= 1000 V AC 50/60 Hz |
Ith Cnvtl Free Air Therm Crrt | 2000 A 104 °F (40 °C) power circuit |
Irms Rated Making Capacity | 15000 A 1000 V AC power circuit IEC 60158-1 15000 A 1000 V AC power circuit IEC 60947-4 |
Rated Breaking Capacity | 12000 A 500 V power circuit IEC 60158-1 12000 A 500 V power circuit IEC 60947-4 15000 A 440 V power circuit IEC 60158-1 15000 A 440 V power circuit IEC 60947-4 5000 A 1000 V power circuit IEC 60158-1 5000 A 1000 V power circuit IEC 60947-4 9000 A 660...690 V power circuit IEC 60158-1 9000 A 660...690 V power circuit IEC 60947-4 |
Associated Fuse Rating | 1600 A aM <= 440 V power circuit 2000 A gI <= 440 V power circuit |
Average Impedance | 0.13 mOhm - Ith 2000 A 50 Hz power circuit |
Power Dissipation Per Pole | 290 W AC-3 - Ith 2000 A 520 W AC-1 - Ith 2000 A |
Inrush Power In VA | 1300 VA |
Hold-In Power Consumption Va | 31 VA 50/60 Hz |
Operating Time | 100...150 ms closing 50...100 ms opening |
Mechanical Durability | 1200000 cycles |
Operating Rate | 120 cyc/h 131 °F (55 °C) |
Height | 19.29 in (490 mm) |
Width | 31.10 in (790 mm) |
Depth | 18.70 in (475 mm) |
Product Weight | 207.23 lb(US) (94 kg) |
Standards | NF C 63-110 IEC 60158-1 BS 5424 VDE 0660 IEC 60947-4 |
Product Certifications | CSA RINA BV |
Protective Treatment | TC TH |
Ambient Air Temp For Op | 23…131 °F (-5…55 °C) |
Ambient Air Temp For Storage | -76…176 °F (-60…80 °C) |
Operating Altitude | 9842.52 ft (3000 m) without derating |
Category | 22341 - CONTACTOR,D,K,&F ACCESS |
Discount Schedule | I12 |
GTIN | 03389110103069 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | FR |
EU RoHs Directive | Compliant |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366