LADN04 is a Schneider Electric add-on auxiliary contact block for TeSys D and TeSys F contactors. Front mounting block, it provides 4NC instantaneous contacts rated up to 10A 690V AC. It can be used in safety applications. LADN04 is a Schneider Electric add-on auxiliary contact block for TeSys D and TeSys F contactors. It provides 4NC instantaneous contacts rated up to 10A 690V AC. It can be used in safety applications thanks to its NC certified mirror contacts. Easy to mount on front by clip-on, it procures high reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Add-on block with 4NC mechanically linked auxiliary contacts, with instantaneous operation. Suitable to be included in the control of safety systems thanks to its NC certified mirror contacts. High electrical durability , several millions of operating cycles in AC-14/AC-15/DC-13 according conditions. Mounting by clip-on on front of all TeSys D and TeSys F contactors.
Add to Quote CataloguePart Number | LADN04 |
---|---|
Country of Origin | FR |
UPC | 785901213673 |
UPC11 | 78590121367 |
EAN | 3389110383904 |
Availability | S |
Lead Time | 3 |
UNSPSC | 39121529 |
ECCN | EAR99 |
HTs Code | 8538908180 |
RoHS Compliant | Yes |
Discount Schedule | I12 |
Return Indicator | Yes |
Depth | 1.65 inch |
Height | 1.89 inch |
Width | 1.73 inch |
Weight | 0.11 pound |
Range | TeSys |
---|---|
Range Of Product | TeSys D |
Device Short Name | LADN |
Product Or Component Type | Auxiliary contact block |
Range Compatibility | TeSys D LC1D TeSys D CAD TeSys F LC1F TeSys F CR1F |
Mounting Location | Front |
Pole Contact Composition | 4 NC |
Contacts Operation | Instantaneous |
Ue Rated Operational Voltage | 690 V AC 25...400 Hz |
Ui Rated Insulation Voltage | 690 V IEC 60947-5-1 600 V CSA 600 V UL |
Ith Cnvtl Free Air Therm Crrt | 10 A 140 °F (60 °C) |
Standards | EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 |
Product Certifications | IECEE CB Scheme UL CSA CCC EAC |
Irms Rated Making Capacity | 140 A AC IEC 60947-5-1 250 A DC IEC 60947-5-1 |
Permissible Short-Time Rating | 100 A 140 °F (60 °C) 1 s 120 A 140 °F (60 °C) 500 ms 140 A 140 °F (60 °C) 100 ms |
Protection Type | GG fuse 10 A |
Mechanical Durability | 30 Mcycles |
Minimum Switching Current | 5 mA |
Minimum Switching Voltage | 17 V |
Non-Overlap Time | 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact |
Insulation Resistance | > 10 MOhm |
Connections - Terminals | screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible with cable end screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)solid screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)solid |
Tightening Torque | 15.05 lbf.in (1.7 N.m) flat Ø 6 mm 15.05 lbf.in (1.7 N.m) Philips No 2 |
Height | 1.89 in (48 mm) |
Width | 1.73 in (44 mm) |
Depth | 1.65 in (42 mm) |
Product Weight | 0.11 lb(US) (0.05 kg) |
Environmental Characteristic | Normal environment |
IP Degree Of Protection | IP20 IEC 60529 |
Protective Treatment | TH IEC 60068 |
Ambient Air Temp For Storage | -76…176 °F (-60…80 °C) |
Ambient Air Temp For Op | 23…140 °F (-5…60 °C) |
Operating Altitude | 9842.52 ft (3000 m) |
Category | 22341 - CONTACTOR,D,K,&F ACCESS |
Discount Schedule | I12 |
GTIN | 00785901213673 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | FR |
Green Premium Status | Green Premium product |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Compliant |
Toxic Heavy Metal Free | Yes |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Warranty | 18 months |