| Part Number | SUVTP20KF3B4S |
|---|---|
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| Depth | 32.01 inch |
| Height | 59.02 inch |
| Width | 20.59 inch |
| Weight | 1183.49 pound |
| Lead Time | Usually Ships within 2 Weeks |
|---|---|
| Provided Equipment | Battery modules ship installed CD with software Network Management Card Power modules ship installed Smart UPS signalling RS-232 cable User Manual Bolt down brackets Installation guide Start up included |
| Colour | Black |
| Depth | 32.01 in (81.3 cm) |
| Height | 59.02 in (149.9 cm) |
| Product Weight | 1183.49 lb(US) (536.82 kg) |
| Width | 20.59 in (52.3 cm) |
| Network Frequency | 40 - 70 Hz |
| Number Of Input Connectors | 1 Hard Wire 5-wire (3PH + N + G) |
| Input Voltage Limits | 165...240 V |
| Inputvolt_Other | 220 V |
| Maximum Input Current | 53 A |
| Switching Current Capacity | 80 A |
| Input Voltage | 3 phase |
| Rated Power In W | 16000 W |
| Max Configurable Power In W | 16000 W |
| Harmonic Distortion | Less than 5 % at full load |
| Output Frequency | 57...63 Hz for 60 Hz nominal sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced |
| Outputvolt_Other | 220 V |
| Crest Factor | Unlimited |
| Ups Type | Double Conversion Online |
| Wave Type | Sine wave |
| Output Connector Type | Hard Wire 5-wire (3PH + N + G) 1 |
| Connections - Terminals | 1 screw terminals |
| Bypass Type | Built-in Maintenance Bypass Built-in Static Bypass |
| Output Voltage | 120 V 208 V 208 V 3 phase |
| Product Certifications | CUL Listed UL 1778 |
| Standards | ISO 14001 ISO 9001 |
| Ambient Air Temp For Op | 32…104 °F (0…40 °C) |
| Relative Humidity | 0…95 % |
| Operating Altitude | 0...3333 ft |
| Ambient Air Temp For Storage | -58…104 °F (-50…40 °C) |
| Storage Altitude | 0…50000 ft (0.00…15240.00 m) |
| Acoustic Level | 55 dBA |
| Heat Dissipation | 4238 Btu/h |
| Nema Degree Of Protection | NEMA 1 |
| Battery Type | VRLA |
| Number Of Battery Filled Slots | 3 |
| Number Of Battery Free Slots | 1 |
| Battery Recharge Time | 5 h |
| Number Of Battery Repl Qty | 1 |
| Additional Information | Configurable for 208 and 220V - 3 Phase |
| Battery Voltage | +/-192 V (split battery referenced to neutral) |
| Discharge Battery Voltage | +/-154 V |
| Preinstalled Device | Network management card 2 with environmental monitoring |
| Control Panel | Multi-function LCD status and control console |
| Alarm | Audible and visible alarms : configurable delays |
| Emergency Power Off | Yes |
Powered by ![]()