| Part Number | SURTD3000XLIM |
|---|---|
| UPC | 731304283546 |
| UPC11 | 73130428354 |
| EAN | 0731304283546 |
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Depth | 25.98 inch |
| Height | 17.01 inch |
| Width | 5.12 inch |
| Weight | 120.26 pound |
| Lead Time | Usually in Stock |
|---|---|
| Provided Equipment | CD with software Relay board Smart UPS signalling RS-232 cable User Manual |
| Cable Length | 8 ft (2.44 m) |
| Number Of Rack Unit | 3U |
| Colour | Black |
| Depth | 25.98 in (66 cm) |
| Height | 17.01 in (43.2 cm) |
| Product Weight | 120.26 lb(US) (54.55 kg) |
| Width | 5.12 in (13 cm) |
| Network Frequency | 50/60 Hz +/- 5 Hz auto-sensing |
| Plug Standard | BS1363A British IEC 60320 C20 Schuko CEE 7 / EU1-16P |
| Input Voltage Limits | 100...280 V adjustable 180...270 V |
| Inputvolt_Other | 220 V 240 V |
| Input Voltage | 230 V |
| Rated Power In W | 2100 W |
| Max Configurable Power In W | 2100 W |
| Harmonic Distortion | Less than 3% |
| Output Frequency | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 sync to mains |
| Outputvolt_Other | 220 V 240 V |
| Crest Factor | 3 : 1 |
| Ups Type | Double Conversion Online |
| Wave Type | Sine wave |
| Nb Of Power Socket Outlets | 8 IEC 60320 2 IEC Jumpers 2 IEC 60320 |
| Bypass Type | Internal Bypass (Automatic and Manual) |
| Output Voltage | 230 V |
| Product Certifications | CE DNV KCC |
| Standards | EN 50091-1 EN 50091-2 EN 55022 Class A EN 60950 EN 61000-3-2 |
| Ambient Air Temp For Op | 32…131 °F (0…55 °C) |
| Relative Humidity | 0…95 % non-condensing |
| Operating Altitude | 0...10000 ft |
| Ambient Air Temp For Storage | 5…113 °F (-15…45 °C) |
| Storage Altitude | 0…50000 ft (0.00…15240.00 m) |
| Acoustic Level | 55 dBA |
| Heat Dissipation | 609 Btu/h |
| IP Degree Of Protection | IP20 |
| Battery Type | Lead-Acid battery |
| Number Of Battery Filled Slots | 2 |
| Battery Recharge Time | 2.5 h |
| Number Of Battery Repl Qty | 1 |
| Additional Information | Configurable for 220 : 230 or 240 nominal output voltage |
| Preinstalled Device | Dry contact I/O smartslot card |
| Control Panel | LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators |
| Alarm | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
| Emergency Power Off | Yes |
| Surge Energy Rate | 555 J |
| Noise Suppression | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : m |
| GTIN | 00731304283546 |
| EU RoHs Directive | Compliant |