| Part Number | 140ACI03000 |
|---|---|
| Country of Origin | FR |
| UPC | 785901792185 |
| UPC11 | 78590179218 |
| EAN | 3595861126565 |
| Availability | S |
| Lead Time | 10 |
| UNSPSC | 32151705 |
| ECCN | EAR99 |
| HTs Code | 8538908180 |
| Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
| RoHS Compliant | Yes |
| Discount Schedule | PC21 |
| Return Indicator | Yes |
| Weight | 0.66 pound |
| Range Of Product | Modicon Quantum automation platform |
|---|---|
| Product Or Component Type | Analogue input module |
| Type Of Filter | Single pole low pass - 3 dB at 15 Hz +/- 20 % |
| Analogue Input Number | 8 |
| Input Type | Differential |
| Addressing Requirement | 9 input words |
| Analogue Input Resolution | 12 bits |
| Linear Measuring Range | 1...5 V 4...20 mA |
| Absolute Maximum Input | 50 V DC 25 mA |
| Input Impedance | 250 Ohm current +/- 0.01 % > 20 MOhm voltage |
| Absolute Accuracy Error | +/- 0.05 % of full scale +/- 0.1 % of full scale maximum |
| Linearity Error | +/- 0.04 % |
| Accr Drift Accg To Temperature | +/- 0.0025 % of full scale/°C <= 0.005 % of full scale/°C |
| Common Mode Rejection | > - 72 dB 60 Hz |
| ISOl Betwn Channels And Bus | 1000 V DC 3000 V DC 60 s |
| ISOlation Between Channels | 30 V DC |
| Update Time | 5 ms |
| Fault Type | Broken wire 4...20 mA Undervoltage range 1...5 V |
| Marking | CE |
| Local Signalling | Bus communication is present (Active) 1 LED green) External fault 1 LED red) Channel is turned on 8 LEDs green) Channel fault 8 LEDs red) |
| Bus Current Requirement | 240 mA |
| Power Dissipation In W | 2 W |
| Module Format | Standard |
| Product Weight | 0.66 lb(US) (0.3 kg) |
| Standards | UL 508 CSA C22.2 No 142 |
| Product Certifications | FM Class 1 Division 2 CUL |
| Resist Electrostatic Dischrg | 4 kV contact IEC 801-2 8 kV on air IEC 801-2 |
| Resist To Electromagn Fields | 9.14 V/m (10 V/m) 80…1000 MHz IEC 801-3 |
| Ambient Air Temp For Op | 32…140 °F (0…60 °C) |
| Ambient Air Temp For Storage | -40…185 °F (-40…85 °C) |
| Relative Humidity | 95 % without condensation |
| Operating Altitude | <= 16404.2 ft (5000 m) |
| Category | 18155 - QUANTUM I/O & POWER SUPPLIES |
| Discount Schedule | PC21 |
| GTIN | 00785901792185 |
| Nbr. Of Units In Pkg. | 1 |
| Country Of Origin | FR |
| Green Premium Status | Green Premium product |
| EU RoHs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
| Mercury Free | Yes |
| WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
| Warranty | 18 months |