Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Advanced power base, TeSys U, 3P, 32A/690V
LUB320
Advanced power base, TeSys U, 3P, 32A/690V

TeSys U advanced power base, 3 poles (3NO), 32A/690V, to be completed with a control unit LUC to form a TeSys U starter controller, for 3-phase motor applications up to 15kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a “all in one” starter controller with basic or advanced protection and control functions. It is equipped with auxiliary signaling contacts (1NO+1NC), a control terminal block, and blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Add to Quote Catalogue
Specifications
Part Number LUB320
Country of Origin FR
UPC 785901221821
UPC11 78590122182
EAN 3389110362800
Availability N
Lead Time 33
UNSPSC 39121521
HTs Code 8536490080
RoHS Compliant Yes
Discount Schedule I11
Return Indicator Yes
Depth 4.96 inch
Height 6.06 inch
Width 1.77 inch
Weight 1.91 pound
Characteristics
Range TeSys
Product Name TeSys U
Device Short Name LUB
Product Or Component Type Non reversing power base
Device Application Motor control Motor protection
Poles Description 3P
Suitability For ISOlation Yes
Ue Rated Operational Voltage 690 V AC power circuit
Network Frequency 40...60 Hz
Ith Cnvtl Free Air Therm Crrt 32 A
Ie Rated Operational Current 32 A <= 440 V 23 A 500 V 21 A 690 V
Utilisation Category AC-44 AC-41 AC-43
Ics Rated Service Breaking Cap 50 kA 230 V 50 kA 440 V 10 kA 500 V 4 kA 690 V
Auxiliary Contact Composition 1 NO + 1 NC
Auxiliary Contacts Type Linked contacts 1 NO + 1 NC) IEC 60947-4-1 Mirror contact 1 NC) IEC 60947-1
[Uc] Control Circuit Voltage 24 V AC 50/60 Hz 24 V DC 48...72 V AC 50/60 Hz 48...72 V DC 110...240 V AC 50/60 Hz 110...220 V DC
Typical Current Consumption 200 mA 24 V DC I maximum while closing with LUCM 220 mA 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD 220 mA 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD 25 mA 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 25 mA 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD 280 mA 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD 280 mA 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD 280 mA 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD 280 mA 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD 45 mA 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD 45 mA 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 75 mA 24 V DC I rms sealed with LUCM 80 mA 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD 90 mA 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
Heat Dissipation 3 W control circuit with LUCA, LUCB, LUCC, LUCD 1.8 W control circuit with LUCM
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Operating Time 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit 50 ms >= 72 V closing with LUCA, LUCB, LUCC, LUCD control circuit 60 ms 48 V closing with LUCA, LUCB, LUCC, LUCD control circuit 70 ms 24 V closing with LUCA, LUCB, LUCC, LUCD control circuit 65 ms closing with LUCM control circuit
Mechanical Durability 15 Mcycles
Operating Rate 3600 cyc/h
Product Certifications CE UL CSA CCC EAC ASEFA ATEX Marine
Standards EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier
Ui Rated Insulation Voltage 690 V IEC 60947-6-2 3) 600 V UL 60947-4-1 600 V CSA C22.2 No 60947-4-1
Uimp Rated Imp Wstd Voltage 6 kVIEC 60947-6-2
Safe Separation Of Circuit 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Fixing Mode Clipped DIN rail) Screw-fixed plate)
Connections - Terminals Power circuit screw clamp terminals 1 0.00…0.02 in² (1…10 mm²) rigid Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 1 0.00…0.02 in² (2.5…10 mm²) flexible without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) flexible with cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) rigid Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end Control circuit without connection
Tightening Torque Control circuit 7.08…10.62 lbf.in (0.8…1.2 N.m) flat 0.20 in (5 mm) Control circuit 7.08…10.62 lbf.in (0.8…1.2 N.m) Philips no 1 0.20 in (5 mm) Power circuit 16.82…22.13 lbf.in (1.9…2.5 N.m) flat 0.24 in (6 mm) Power circuit 16.82…22.13 lbf.in (1.9…2.5 N.m) Philips No 2 0.24 in (6 mm)
Width 1.77 in (45 mm)
Height 6.06 in (154 mm)
Depth 4.96 in (126 mm)
Product Weight 1.91 lb(US) (0.865 kg)
Compatibility Code LUB
IP Degree Of Protection IP20 IEC 60947-1 front panel and wired terminals) IP20 IEC 60947-1 other faces) IP40 IEC 60947-1 front panel outside connection zone)
Protective Treatment TH IEC 60068
Ambient Air Temp For Op -13…140 °F (-25…60 °C) with LUCM -13…158 °F (-25…70 °C) with LUCA, LUCB, LUCC, LUCD
Ambient Air Temp For Storage -40…185 °F (-40…85 °C)
Fire Resistance 1760 °F (960 °C) parts supporting live components IEC 60695-2-12 1202 °F (650 °C) IEC 60695-2-12
Operating Altitude 6561.68 ft (2000 m)
Shock Resistance 10 gn power poles open IEC 60068-2-27 15 gn power poles closed IEC 60068-2-27
Vibration Resistance 2 gn 5…300 Hz) power poles open IEC 60068-2-27 4 gn 5…300 Hz) power poles closed IEC 60068-2-27
Resist Electrostatic Dischrg 8 kV 3 in open air IEC 61000-4-2 8 kV 4 on contact IEC 61000-4-2
Resistance To Radiated Fields 9.14 V/m (10 V/m) 3 IEC 61000-4-3
Resistance To Fast Transients 2 kV 3 serial link IEC 61000-4-4 4 kV 4 all circuits except for serial link IEC 61000-4-4
Non-Dissipating Shock Wave 1 kV serial mode 24...240 V AC IEC 60947-6-2 1 kV serial mode 48...220 V DC IEC 60947-6-2 2 kV common mode 24...240 V AC IEC 60947-6-2 2 kV common mode 48...220 V DC IEC 60947-6-2
Imm To Radioelectric Fields 10 V IEC 61000-4-6
Immunity To Microbreaks 3 ms control circuit
Immunity To Voltage Dips 70 % / 500 ms IEC 61000-4-11
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews