This hardware is an active power correction solution, from AccuSine familly, to help stabilize electrical networks by providing harmonic mitigation and power factor correction, and load balancing. It is specifically designed for harsh electrical conditions, for heavy industrial applications including mission critical environments. This version is UL Type OPEN, or ingress protection IP00, and can be connected on Low Voltage networks rated 380 Volt to 480 Volt. It is specified for a standard Root Mean Square output current rating of 60 Amps. The enclosure is wall mounted, allow cable entry from bottom and is delivered in RAL7035 light grey. This active power filter achieves above standards performance THDi less or equal to 3%, is certified to CE, UL, IBC 2015 AC156, EAC, RCM. And is designed to IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4, IEC 61439-1, UL508 and IEEE 519-2014. Up to 10 units of different ratings can be paralleled, to achieve a maximum compensation of 3000A per CT set. Frame exterior dimensions are 421 millimetres in width, 349 millimetres in depth, 1300 millimetres in height and product weight 88 kg.
Brand: Square D
Add to Quote CataloguePart Number | PCSP060D5IP00 |
---|---|
Country of Origin | US |
UPC | 606480850998 |
UPC11 | 60648085099 |
EAN | 3606480850998 |
Availability | N |
Lead Time | 30 |
UNSPSC | 83101808 |
ECCN | EAR99 |
HTs Code | 8543709960 |
RoHS Compliant | Yes |
Discount Schedule | DE2C |
Return Indicator | No |
Depth | 13.74 inch |
Height | 51.18 inch |
Width | 16.57 inch |
Weight | 198.42 pound |
Range Of Product | AccuSine |
---|---|
Product Name | AccuSine PCS+ |
Product Or Component Type | Active harmonic filter |
Network Type | 3P |
Network Configuration | 3 or 4 wires |
Network Rated Voltage | 380…480 V AC |
Network Frequency | 50/60 Hz +/- 3 Hz auto sensing |
Maximum Permissible Voltage | 1.1 x Un |
Neutral Correction | Not provided |
Rms Output Current Rating | 60 A |
Reactive Power Rating | 50 kvar 480 V AC 50/60 Hz |
Operating Modes | Harmonic cancellation Mains current balancing Power factor correction |
Installation Location | Indoor |
Enclosure Mounting | Wall mounted |
Protection Type | Without protection |
Heat Dissipation | Rear plenum with forced ventilation for high heat flow |
Electromagnetic Compatibility | Conducted EMC, class A EN 61000-6-4 |
Accessibility For Operation | Front |
Location Of Connection | Bottom |
Enclosure Degree Of Protection | IP00 |
Environmental Characteristic | Operating 3C2 IEC 60721-3-3 Operating 3S2 IEC 60721-3-3 Storage 3C3 IEC 60721-3-3 Storage 3S3 IEC 60721-3-3 |
Operating Altitude | <= 3280.84 ft (1000 m) 1 % per 100 m |
Ambient Air Temp For Op | 32…104 °F (0…40 °C) 32…122 °F (0…50 °C) maximum with current derating of 2 % per °C |
Relative Humidity | 0…95 % |
Pcba Protection | Conformal coated |
Standards | UL 508 CSA C22.2 No 60947-1-07 UL 60947-1 EN 61000-6-4 EN 60439-1 CSA C22.2 No 14 |
Product Certifications | DNV-GL ABS RCM CE CULus |
Ambient Air Temp For Storage | -4…140 °F (-20…60 °C) |
Product Weight | 198.42 lb(US) (90 kg) |
Height | 51.18 in (1300 mm) |
Width | 16.57 in (421 mm) |
Colour | Light gray RAL 7035) |
Depth | 13.74 in (349 mm) |
Category | 00089 - ACTIVE FILTERS |
Discount Schedule | DE2C |
GTIN | 03606480850998 |
Nbr. Of Units In Pkg. | 1 |
Country Of Origin | US |
Green Premium Status | Green Premium product |
REACh Free Of SVHC | Yes |
EU RoHs Directive | Compliant |
Toxic Heavy Metal Free | Yes |
Mercury Free | Yes |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Warranty | 18 months |
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366