Voltage Class 25 KV, Application ø 6.5-220 MM, BPTM-235/130-A/U-4
BPTM-235/130-A/U-4
Voltage Class 25 KV, Application ø 6.5-220 MM, BPTM-235/130-A/U-4

TE Connectivity’s (TE) Raychem BPTM medium-wall, heat shrink tubing provides insulation enhancement and protection against flashover and accidentally induced discharge.

Particularly useful in confined spaces, the BPTM tubing can be used on both circular and rectangular copper or aluminium busbars.

On application of heat, the tubing shrinks snugly over the busbar profile, ensuring that the required minimum wall thickness is obtained. TE’s Raychem BPTM tubing can be installed easily during large scale production using an oven or in the field using a gas torch or hot air.

The BPTM tubing is manufactured from a halogen-free based polymer which has excellent performance in high voltage environments and greatly reduces the noxious and corrosive effects in fire situations.

Use of the BPTM tubing allows equipment designers the freedom to reduce air spacing between busbars, such as in the manufacture of switchgear cabinets where space is at a premium. The BPTM tubing provides flashover protection up to 25 kV.

KEY FEATURES

  • Exceptional insulation and longterm reliability even at high continuous operating temperatures
  • Suitablefor indoor and outdoor use
  • Excellentanti-tracking properties
  • Flameretardant and halogen-free
  • Goodthermal emissivity
  • Long shelf life and can be stored at temperatures up to 50°C without loss of performance
  • REACHand RoHS compliant
  • ULapproved

Brand: TE Connectivity

Add to Quote Download Spec Sheet PDF
Product Selection
Ordering description Rectangular bars L + T mm (in) Round bars D mm (in) Inside diameter mm (in) Wall thickness mm (in)  UOM: roll of length m (ft)
min. max. min. max. H min. h max. W nom. w min.
BPTM-15/6-A/U-4 12 (0.47) 18 (0.71) 6.5 (0.25) 12 (0.47) 15 (0.59) 6 (0.24) 1.1 (0.04) 1.90 (0.07) 30 (98.43)
BPTM-30/12-A/U-4 22 (0.87) 38 (1.50) 13.5 (0.53) 25 (0.98) 30 (1.18) 12 (0.47) 1.1 (0.04) 2.20 (0.09) 30 (98.43)
BPTM-50/20-A/U-4 36 (1.42) 65 (2.56) 22 (0.87) 43 (1.69) 50 (1.97) 20 (0.79) 1.1 (0.04) 2.35 (0.09) 30 (98.43)
BPTM-75/30-A/U-4 55 (2.17) 95 (3.74) 33 (1.30) 63 (2.48) 75 (2.95) 30 (1.18) 1.1 (0.04) 2.35 (0.09) 20 (65.62)
BPTM-100/40-A/U-4 70 (2.76) 130 (5.12) 44 (1.73) 86 (3.39) 100 (3.94) 40 (1.57) 1.1 (0.04) 2.35 (0.09) 25 (82.02)
BPTM-120/50-A/U-4 90 (3.44) 165 (6.50) 55 (2.17) 105 (4.13) 120 (4.72) 50 (1.97) 1.3 (0.05) 2.80 (0.11) 25 (82.02)
BPTM-175/70-A/U-4 125 (4.92) 235 (9.25) 80 (3.15) 150 (5.91) 170 (6.69) 70 (2.76) 1.3 (0.05) 2.80 (0.11) 15 (49.21)
BPTM-205/110-A/U-4 200 (7.87) 276 (10.87) 127 (5.00) 190 (7.48) 205 (8.07) 110 (4.33) 1.3 (0.05) 2.80 (0.11) 10 (32.81)
BPTM-235/130-A/U-4 235 (9.25) 315 (12.40) 150 (5.91) 220 (8.66) 235 (9.25) 130 (5.12) 1.5 (0.06) 3.10 (0.12) 20 (65.62)

 

Technical Report
EDR 5537 BPTM Tubing Qualification Report
PPR 3320 BPTM Material Thermal endurance Test Report
UVR 8122 Resistance of BBIT/BPTM to Hydrofluoric acid
20180627

E498737

BPTM UL Certificate
Specifications
Thermal endurance 125°C min. (257°F min.)
Accelerated ageing 168 hrs @ 150°C (302°F)
- Tensile strength 10 MPa min.
- Ultimate elongation 300% min.
Inclined tracking test No tracking or erosion 1hr @ 2.5 kV 1hr @ 2.75 kV
Dielectric strength 350 kV/cm min. @ 1.00 mm (889 v/mil min. @ 0.04 in) 180 kV/cm min. @ 2 mm (457.2 v/mil min. @ 0.08 in) 150 kV/cm min. @ 2.5 mm (492.12 v/mil min. @ 0.10 in) 120 kV/cm min. @ 3 mm (393.70 v/mil min. @ 0.12 in)
Volume resistivity 1E+1014 cm
Low temperature flexibility No cracking after 4 hrs @ -40°C (-40°F)
Smoke index Less than 120
Acid gas generation Less than 1% by weight
Flammability No flame, conveyance 60 sec. max.