Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
Busbar Insulation Tubing (BBIT) up to 36 kV – BBIT-100/40-A/U-4
Busbar Insulation Tubing (BBIT) up to 36 kV – BBIT-100/40-A/U-4

TE Connectivity’s (TE) Raychem BBIT thick-wall, heat shrink tubing provides insulation enhancement and protection against flashover and accidentally induced discharge.

Particularly useful in confined spaces, TE’s Raychem BBIT tubing can be used on both circular and rectangular copper or aluminium busbars.

On application of heat, the tubing shrinks snugly over the busbar profile ensuring that the required minimum wall thickness is obtained. The BBIT tubing can be installed easily during large scale production using an oven or in the field using a gas torch or hot air. The BBIT tubing is manufactured from a halogen-free based polymer which has excellent performance in high voltage environments and reduces the noxious and corrosive effects in fire situations.

The use of the BBIT tubing allows equipment designers the freedom to reduce air spacing between busbars such as in the manufacture of switchgear cabinets where space is at a premium. The BBIT tubing provides flashover protection up to 36 kV.

Brand: TE Connectivity

Get a Quote Download Spec Sheet PDF
PRODUCT SELECTION ORDERING INFORMATION
Ordering description Rectangular bars L + T mm (in) Round bars D m (in) Inside diameter mm (in) Wall thickness mm (in) UOM: roll of length m (ft)
min. max. min. max. H min. h max. W nom. w min.
BBIT-100/40-A/U-4 69 (2.72) 102 (402) 44 (1.73) 72 (2.83) 100 (3.94) 40 (1.57) 1.6 (0.06) 3.6 (0.14) 15 (49.21)

 

 

Specifications
Key Features •Exceptional insulation and long term reliability even at high continuous operating temperatures •Suitable for indoor and outdoor use •Excellent anti-tracking properties •Flame retardant and halogen-free •Good thermal emissivity •Long shelf life and can be stored at temperatures up to 50°C without loss of performance •REACH and RoHS compliant •UL approved
Thermal endurance 125°C min. (257°F min.)
Accelerated ageing 168 hrs @ 150°C (302°F)
Inclined tracking test No tracking or erosion 1hr @ 2.5 kV 1hr @ 2.75 kV
Dielectric strength 350 kV/cm min. @ 1.00 mm (889 v/mil min. @ 0.04 in) 180 kV/cm min. @ 2.00 mm (450 v/mil min. @ 0.08 in) 150 kV/cm min. @ 2.50 mm (381 v/mil min. @ 0.10 in) 120 kV/cm min. @ 3.00 mm (304.80 v/mil @ 0.12 in)
Volume resistivity 1E+1014 cm
Low temperature flexibility No cracking after 4 hrs @ -40°C (-40°F)
Smoke index Less than 120
Acid gas generation Less than 1% by weight
Flammability No flame conveyance, 60 sec. max.
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews