STP T2 40 is the series of Type 2/Class II devices for discharging
voltage surges, in accordance with EN/IEC 61643-11 and certified UL
1449 4th Ed. Suitable for the second stage of protection in supply
distribution panels in which Type 1 protection devices are installed
upstream, or for the first stage of protection in commercial or other
applications not exposed to direct strikes and with no external
lightning protection system.
Brand: Surge-Trap®
Add to Quote| Item Number | 83020123 |
|---|---|
| EAN UPC Code | 8435297849209 |
| GTIN Sell Pack | 38435297849200 |
| Applications |
|
| Approvals Standards |
|
| Brand Name | Mersen |
| Country Of Origin | ES |
| Degree Of Protection Ip | IP20 |
| Features Benefits |
|
| IEC SPD Type | Type 2 / Class II |
| Max Operating Temp | 85 °C |
| Min Operating Temp | -40 °C |
| Product Line | Surge-Trap® Pluggable STPT2 Series - 40kA |
| Product Brand | Surge-Trap® |
| Product Family | Surge Protection |
| Product Group | Power Line SPD - DIN-RAIL IEC TYPE 2/UL CSA |
| Short Circuit Current Rating SCCR | 50 ... 100 kA |
| Short Circuit Withstand ISCCR | 25 kA |
| Wire Type | Rigid: 6…35mm² / Stranded: 6…25mm² |
| Housing Material | PA66 CT1; V-0 |
| Indication System | 1 |
| Indication System Type | Visual Indicator, Microswitch / 3 pin dry contact |
| Max Back-up Fuse | 125 A gG |
| Number Of Poles | 2-Pole |
| Product Height | 3.54 in |
| Product Length | 2.76 in |
| Product Weight | 0.54 lb |
| Product Width | 1.42 in |
| Response Time | 25 ns |
| Sell Pack Description | Box |
| Sell Pack Height | 3.15 in |
| Sell Pack Length | 4.13 in |
| Sell Pack Width | 1.77 in |
| Sell Pack Quantity | 1 EACH |
| Sell Pack Weight | 0.54 lb |
| AC Or DC | AC |
| Catalogue No | STPT2-40K275V-2PM |
| Item Description | STPT2-40K275V-2PM |
| Max Discharge Current Imax 8 20 | 40kA |
| MCOV L-g | 275 V |
| MCOV L-n | 275 V |
| MCOV N-g | 275 V |
| Nominal Discharge Current | 20kA |
| Nominal Operating Volt Rating Un | 230 V |
| Order Multiple | 1 |
| Replacement Plug L-n | SP2-40K275V |
| Short Description | SPD Type 2, 40kA, Uc275V, 2+0 TNS, 2 Poles, 2 Modules, Pluggable, Remote |
| Suitable For Outdoor Use | 0 |
| System Configuration | TT. TNS |
| Torque Rating | 35.4 lb-in |
| Uc L-pe | 275 V |
| Uc L- Pe | 275 V |
| Up At In L-pe | ≤1.3 kV |
| VPR L-g | 900 V |
| VPR L-n | 1800 V |
| VPR N-g | 900 V |
| Suitable For Outdoor Use | 0 |