DR50 INLET POLY BLACK SIZE 3 TYPE 4X 2P+N+G 50A 125/250 VAC 60 Hz NO AUX
Brand: Meltric
Add to Quote| Part Number | 35-38176-K07-HAZ | 
|---|---|
| Model | Zone 2 | 
| Product Type | Hazardous Location | 
| Description | INLET | 
| Brand | Meltric | 
| Rated Current | 50A | 
|---|---|
| Rated Voltage | 125/250 VAC | 
| Contact Configuration | 2P+N+G | 
| Application | Hazardous Location | 
| Environmental Rating | Type 4X | 
| Multipin Current | 50A | 
| Haz Location | CSA Class I Div 2 | 
| Frequency | 60 Hz | 
| Current Interupting Rating | NON-CURRENT INTERRUPTING | 
| Keying Position | 17 | 
| Material | POLY | 
| Product Color | BLACK | 
| Voltage Color Code | ORANGE | 
| Load Break Normal Oper | 50A | 
| Load Break Abnormal Overload | 75A | 
| Nema Watertightness | 4X | 
| Minimum Operating Temperature (C) | -40C | 
| Maximum Operating Temperature (C) | 40C | 
| Minimum Operating Temperature (F) | -40F | 
| Maximum Operating Temperature (F) | 104F | 
| Short Circuit Rating | 100 KA - MAKE & WITHSTAND | 
| Short Circuit Rating Fusing | 100 KA 125A (250%) RK1 NTD | 
| Number Of Auxiliary Contacts | NO AUX | 
| Impact Rating | IK08 | 
| Prod Wire Temp Rtg | 60C | 
| Phase Term Type | SCREW TERMINAL | 
| Phase Term Wire Cap Min Thhn | 14 AWG | 
| Phase Term Wire Cap Max Thhn | 4 AWG | 
| Phase Term Wire Cap Min Type W | 14 AWG | 
| Phase Term Wire Cap Max Type W | 4 AWG | 
| Phase Cond Strip Len | 7/8 IN OR 22 MM | 
| Phase Term Tightening Torq | 15 IN-LBS / 1.7 N-M | 
| Csa Listing | cCSAus | 
| Csa List File | 208161 | 
| Csa List Std 1 | C22.2 No. 182.1-07 | 
| Csa List Std 2 | C22.2 No. 213-M1987 | 
| Instructions | INSZONE2 | 
| Num Notch Pos | 24 | 
| Mating Box | MB3 | 
| Product Ln | 46 | 
Powered by ![]()
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366