Bussmann’s UL Class RK5 Fusetron product offering provides energy efficient advanced protection with its dual-element, time-delay construction and is available with optional open fuse indication on select ratings. Available in both 250Vac and 600Vac, 200kA RMS Sym interrupting rating and sizes ranging from 0 to 600 amp. Fusetron’s deliver 10 seconds (minimum) of time-delay at 500% of rated current (8 seconds for 1/10-30A sizes).
Eaton Bussmann series RK5SK fuse, Branch circuit, Class RK5, Non-indicating, Standard, 250 V, 600 V
Brand: Eaton
Add to Quote| Catalog Number | RK5SK-39 |
|---|---|
| Brand | Eaton |
| Sub Brand | Bussmann Series |
| Product Type | Fuse |
| Product Feature | Current limiting provides component short-circuit protection|Insulated end caps for 225A-600A fuses reduces exposure to live parts and extends air gap to distance between blades of adjacent mounted fuses or to housing|Superior overload and cycling capabilities|Separate overload and short-circuit elements provide time delay for sizing as close as 125% of motor FLA while delivering excellent short-circuit protection|2:1 selective coordination amp ratio (within the Bussmann series RK5 fuse family) prevents overcurrent events from opening upstream Fusetron fuses |
| Product Shape | Rectangular |
| Product Height | 0.001 inch |
| Product Width | 0.001 inch |
| Product Length | 0.001 inch |
| Product Weight | 8.7 pound |
| Warranty | Not Applicable |
| Compliances |
|
| Product Function |
|
| Application | Branch circuit |
|---|