Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
ATV630D22M3 – Variable speed drive, Altivar Process ATV600, ATV630, 22kW/30 hp, 200…240 V, IP21/UL type 1
ATV630D22M3
variable speed drive, Altivar Process ATV600, ATV630, 22kW, 30hp, 200 to 240V, IP21, UL type 1

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 200V to 240V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 22kW / 30hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 18.5kW / 25hp for applications requiring significant overload (up to 150%). It weighs 14.3kg and its dimensions are, 226mm wide, 673mm high, 271mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Prospective Line Isc 50 kA
Product Destination
  • asynchronous motors
  • synchronous motors
Line Current
  • 76 A 200 V normal duty)
  • 64.3 A 240 V normal duty)
  • 64.8 A 200 V heavy duty)
  • 54.5 A 240 V heavy duty)
Emc Filter without EMC filter
Asynchronous Motor Control Profile
  • variable torque standard
  • constant torque standard
  • optimized torque mode
Variant standard version
Product Or Component Type variable speed drive
Apparent Power
  • 26.7 kVA 240 V normal duty)
  • 22.7 kVA 240 V heavy duty)
Switching Frequency
  • 2...12 kHz adjustable
  • 4...12 kHz with derating factor
Communication Port Protocol
  • Modbus TCP
  • Ethernet
  • Modbus serial
Product Specific Application process and utilities
Safety Function STO (safe torque off) SIL 3
Maximum Horse Power Rating
  • 30 hp normal duty
  • 25 hp heavy duty
Supply Frequency 50...60 Hz - 5...5 %
Option Card
  • slot A communication module, Profibus DP V1
  • slot A communication module, PROFINET
  • slot A communication module, DeviceNet
  • slot A communication module, Modbus TCP/EtherNet/IP
  • slot A communication module, CANopen daisy chain RJ45
  • slot A communication module, CANopen SUB-D 9
  • slot A communication module, CANopen screw terminals
  • slot A/slot B digital and analog I/O extension module
  • slot A/slot B output relay extension module
  • slot A communication module, Ethernet IP/Modbus TCP/MD-Link
  • communication module, BACnet MS/TP
  • communication module, Ethernet Powerlink
Degree Of Protection UL type 1 UL 508C
Range Of Product Altivar Process ATV600
Speed Drive Output Frequency 0.1-500 Hz
Ip Degree Of Protection
  • IP21IEC 61800-5-1
  • IP21IEC 60529
Motor Power Kw
  • 22 kW normal duty)
  • 18.5 kW heavy duty)
[Us] Rated Supply Voltage 200...240 V
[Us] Rated Supply Voltage 200...240 V - 15...10 %
Discrete Input Logic 16 preset speeds
Type Of Cooling forced convection
Continuous Output Current
  • 92.6 A 4 kHz normal duty
  • 78.4 A 4 kHz heavy duty
Nominal Switching Frequency 4 kHz
Device Short Name ATV630
Synchronous Motor Control Profile
  • permanent magnet motor
  • synchronous reluctance motor
Discrete Input Logic
  • positive logic (source) DI1...DI8), < 5 V, > 11 V
  • negative logic (sink) DI1...DI8), > 16 V, < 10 V
Analogue Output Type
  • software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits
  • software-configurable current AQ1, AQ2 0...20 mA 10 bits
  • software-configurable current DQ-, DQ+ 30 V DC
  • software-configurable current DQ-, DQ+ 100 mA
Discrete Output Type
  • relay outputs R1A, R1B, R1C 250 V AC 3000 mA
  • relay outputs R1A, R1B, R1C 30 V DC 3000 mA
  • relay outputs R2A, R2C 250 V AC 5000 mA
  • relay outputs R2A, R2C 30 V DC 5000 mA
  • relay outputs R3A, R3C 250 V AC 5000 mA
  • relay outputs R3A, R3C 30 V DC 5000 mA
Maximum Switching Current
  • relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC
  • relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC
  • relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
  • relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Exchange Mode half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Power Range 15-25 kW 200-240 V 3 phase
Phase 3 phase
Net Weight 14.3 kg
Type Of Polarization no impedance
Relay Output Type
  • configurable relay logic R1 fault relay NO/NC 100000 cycles
  • configurable relay logic R2 sequence relay NO 100000 cycles
  • configurable relay logic R3 sequence relay NO 100000 cycles
Frequency Resolution
  • display unit 0.1 Hz
  • analog input 0.012/50 Hz
Maximum Transient Current
  • 101.9 A 60 s normal duty)
  • 117.6 A 60 s heavy duty)
Analogue Input Number 3
Motor Slip Compensation
  • adjustable
  • automatic whatever the load
  • not available in permanent magnet motor law
  • can be suppressed
Discrete Output Number 0
Method Of Access slave Modbus TCP
Discrete Input Number 8
Local Signalling
  • for local diagnostic 3 LEDs
  • for embedded communication status 3 LEDs (dual colour)
  • for communication module status 4 LEDs (dual colour)
  • for presence of voltage 1 LED (red)
Linearity Error
  • AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
  • AO1, AO2 +/- 0.2 % analog output
Number Of Addresses 1-247 Modbus serial
Width 226 mm
Transmission Rate
  • 10, 100 Mbits
  • 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Depth 271 mm
Analogue Input Type
  • AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits
  • AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits
  • AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete And Process Manufacturing
  • building - HVAC compressor centrifugal
  • food and beverage processing other application
  • mining mineral and metal fan
  • mining mineral and metal pump
  • oil and gas fan
  • water and waste water other application
  • building - HVAC screw compressor
  • food and beverage processing pump
  • food and beverage processing fan
  • food and beverage processing atomization
  • oil and gas electro submersible pump (ESP)
  • oil and gas water injection pump
  • oil and gas jet fuel pump
  • oil and gas compressor for refinery
  • water and waste water centrifuge pump
  • water and waste water positive displacement pump
  • water and waste water electro submersible pump (ESP)
  • water and waste water screw pump
  • water and waste water lobe compressor
  • water and waste water screw compressor
  • water and waste water compressor centrifugal
  • water and waste water fan
  • water and waste water conveyor
  • water and waste water mixer
Sampling Duration
  • 2 ms +/- 0.5 ms DI1...DI4) - discrete input
  • 5 ms +/- 1 ms DI5, DI6) - discrete input
  • 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input
  • 10 ms +/- 1 ms AO1) - analog output
Electrical Connection
  • control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16
  • line side screw terminal 35...50 mm² AWG 2...AWG 1
  • motor screw terminal 50 mm² AWG 1
Maximum Output Frequency 500 kHz
Height 673 mm
Acceleration And Deceleration Ramps linear adjustable separately from 0.01...9999 s
Transmission Frame RTU
Relay Output Number 3
Data Format 8 bits, configurable odd, even or no parity
Accuracy
  • +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
  • +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Connector Type
  • RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
  • RJ45 on the remote graphic terminal)Modbus serial
Input Compatibility
  • DI1...DI6 discrete input level 1 PLC EN/IEC 61131-2
  • DI5, DI6 discrete input level 1 PLC IEC 65A-68
  • STOA, STOB discrete input level 1 PLC EN/IEC 61131-2
Permissible Temporary Current Boost
  • 1.1 x In 60 s normal duty)
  • 1.5 x In 60 s heavy duty)
Mounting Mode wall mount
Analogue Output Number 2
Physical Interface
  • Ethernet
  • 2-wire RS 485
Minimum Switching Current relay output R1, R2, R3 5 mA 24 V DC
Refresh Time relay output R1, R2, R3)5 ms +/- 0.5 ms)
Enclosure Mounting wall mounted
Isolation between power and control terminals
Output Voltage <= power supply voltage
Quantity Per Set 1
Braking To Standstill by DC injection
Discrete Input Type DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Protection Type
  • thermal protection motor
  • safe torque off motor
  • motor phase break motor
  • thermal protection drive
  • safe torque off drive
  • overheating drive
  • overcurrent between output phases and earth drive
  • overload of output voltage drive
  • short-circuit protection drive
  • motor phase break drive
  • overvoltages on the DC bus drive
  • line supply overvoltage drive
  • line supply undervoltage drive
  • line supply phase loss drive
  • overspeed drive
  • break on the control circuit drive
Supply
  • external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection
  • internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection
  • internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
Mercury Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Upgradeability Upgraded components available
Rohs Exemption Information Yes
Environmental Disclosure ENVPEP1411001EN
Sustainable Offer Status Green Premium product
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile ENVEOLI1411001EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • DNV-GL
  • ATEX zone 2/22
  • CSA
  • TÜV
  • UL
  • ATEX INERIS
Power Dissipation In W
  • natural convection 107 W 200 V 4 kHz
  • forced convection 707 W 200 V 4 kHz
Standards
  • UL 508C
  • EN/IEC 61800-3
  • EN/IEC 61800-3 environment 1 category C2
  • EN/IEC 61800-3 environment 2 category C3
  • EN/IEC 61800-5-1
  • IEC 61000-3-12
  • IEC 60721-3
  • IEC 61508
  • IEC 13849-1
Insulation Resistance > 1 MOhm 500 V DC for 1 minute to earth
Shock Resistance 15 gn 11 ms IEC 60068-2-27
Vibration Resistance
  • 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6
  • 1 gn 13-200 Hz)IEC 60068-2-6
Noise Level 63.5 dB 86/188/EEC
Regulation Loop adjustable PID regulator
Operating Altitude
  • <= 3280.84 ft (1000 m) without derating
  • 1000...4800 m with current derating 1 % per 100 m
Overvoltage Category III
Pollution Degree 2
Electromagnetic Compatibility
  • electrostatic discharge immunity test level 3 IEC 61000-4-2
  • radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
  • electrical fast transient/burst immunity test level 4 IEC 61000-4-4
  • 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
  • conducted radio-frequency immunity test level 3 IEC 61000-4-6
Ambient Air Temperature For Operation
  • -15-50 °C without derating)
  • 50-60 °C with derating factor)
Volume Of Cooling Air 240 m3/h
Marking CE
Pollution Degree 2 EN/IEC 61800-5-1
Noise Level 63.5 dB
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 5-95 % without condensation IEC 60068-2-3
Operating Position vertical +/- 10 degree
Maximum Thdi <48 % from 80...100 % of load IEC 61000-3-12
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews