TeSys GV motor circuit breaker, 3 poles (3P), 32A/690V, for 3-phase motor applications 15kW@400V. It provides a magnetic protection with a tripping level at 14xIn, high breaking capacity Icu 100kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary handle guaranteed for 50 000 cycles AC-3. To complete motor protection, use it in association with a thermal overload relay LRD332 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Product Or Component Type motor circuit breaker
Product Name
  • TeSys GV3
  • TeSys Deca
Range TeSys Deca
Device Application motor protection
Device Short Name GV3L
Trip Unit Technology magnetic
Warranty 18 months
Line Rated Current 32 A
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz IEC 60947-2
Height 132 mm
Network Type AC
Magnetic Tripping Current 448-448 A
Motor Power Kw
  • 15-15 kW 400/415 V AC 50/60 Hz
  • 18.5-18.5 kW 500 V AC 50/60 Hz
  • 22-22 kW 690 V AC 50/60 Hz
Utilisation Category category A IEC 60947-2
Net Weight 0.96 kg
Fixing Mode
  • 35 mm symmetrical DIN rail clipped
  • panel screwed with 3 x M4 screws)
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-2
[Ics] Rated Service Short-Circuit Breaking Capacity
  • 100 % 230/240 V AC 50/60 Hz
  • 100 % 400/415 V AC 50/60 Hz
  • 100 % 440 V AC 50/60 Hz
  • 50 % 500 V AC 50/60 Hz
  • 50 % 690 V AC 50/60 Hz
Control Type rotary handle
Power Dissipation Per Pole 8 W
Electrical Durability 50000 cycles AC-3 415 V In
[Ui] Rated Insulation Voltage 690 V AC 50/60 Hz IEC 60947-2
Breaking Capacity
  • 100 kA Icu 230/240 V AC 50/60 Hz
  • 100 kA Icu 400/415 V AC 50/60 Hz
  • 50 kA Icu 440 V AC 50/60 Hz
  • 12 kA Icu 500 V AC 50/60 Hz
  • 6 kA Icu 690 V AC 50/60 Hz
Suitability For Isolation yes IEC 60947-1
Tightening Torque 5 N.m screw clamp terminal
Mechanical Durability 50000 cycles
Poles Description 3P
Color dark grey
Width 55 mm
Depth 136 mm
Network Frequency 50/60 Hz
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP060901
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI060901
Eu Rohs Directive Compliant
Product Certifications
  • CCC
  • UL
  • CSA
  • EAC
  • LROS (Lloyds register of shipping)
  • BV
  • ABS
  • DNV-GL
  • UKCA
Mechanical Robustness
  • shocks 15 Gn for 11 ms contactor open
  • shocks 30 Gn for 11 ms contactor closed
  • vibrations 4 Gn, 5...300 Hz
Ambient Air Temperature For Operation -20-60 °C
Standards
  • EN/IEC 60947-2
  • EN/IEC 60947-4-1
  • UL 60947-4-1
  • CSA C22.2 No 60947-4-1
Climatic Withstand IACS E10
Ambient Air Temperature For Storage -40-80 °C
Ip Degree Of Protection IP20 IEC 60529
Operating Altitude 9842.52 ft (3000 m)
Fire Resistance 960 °C IEC 60695-2-11